SF6 Gas Density Monitor

SF6-DS series

SF6 GAS DENSITY MONITER

SF6-DS series



*Product Overview 


SF6-DS SF6 density controller has installed electric contact device with temperature compensation system. The two contact points are warning point and closedown point, combine with monitor and automatically warning system. 

When SF6 gas divulges, internal pressure reduces and causes the indicator contact (move touch) with the lower limit point (fixed touch) will send out the alarm. If the density of SF6 gas continues to drop to the danger level, the indicator contact (move touch) with the closedown point (fixed touch) will shut-off circuit breaker switch automatically to prevent accident occur. 


*SPECIFICATIONS 

Dial Diameter:100mm 

Case: 
Size-145 x 136 x 88mm 
Material-Stainless steel 304;IP65 
Sealability-10-9Pa.m3/s 

Lens:Safety glass 

Pointer: 
Material-aluminum or stainless steel 
1 black pressure indicator;2 red setting indicators 

Pressure Range:-76cmHg~9 kg/cm2、-76cmHg~10 kg/cm2 

Accuracy:±1.5% F.S.(-30~+60℃);±2.5%F.S.(-40℃) 

Measuring Element:Stainless steel 316L 

Mounting Type: 
Direct mounting-Bottom connection;Back connection without flange 
Flush panel mounting-Back connection with flange 

Connection: 
Port material:SUS316 
1/8";1/4";3/8";1/2" PT/NPT/PF;G1/2"B male thread 

Dielectric strength:2KV,50Hz 1s or more (for circuit inside) 

Contact Point: 
Rating-30VA/50W 
Material-80%Silver+20%Nickel+10μm gold plated 

Max. Voltage:AC380;DC220V 

Max. Current:1A 

Filling:Without filling;Insulating oil filled 

Shock Proof:300 m/s2 

Vibration Proof:V ‧ H ‧ 5 Grade 

Temperature:Operation -30~+60℃/-22~+140℉ (Option:-40~+60℃) 

※Ordering information 
1. Liquid filled density monitor should be used where vibrations and shocks exit. 
2. When order specify following pressure values: 
(1) Working pressure value (2) Alarm pressure value (3) Lock pressure value

Use of Data
We use cookies to process data, such as your IP address, for content personalization, advertising, and analytics.Usage data may be shared with our partners and combined with other information.
By using this site, you agree. Taiwantrade & iDealEZ’s Privacy Policy

Welcome to Taiwantrade.com

Taiwantrade.com and iDealEZ.com uses analytical cookies and other tracking technologies to offer you the best possible user experience. By using our website, you acknowledge and agree to our cookie policy.

For more information on cookies or changing your cookies settings, read Taiwantrade & iDealEZ’s Privacy Policy.